Calculate ground resistance from rod count, length, diameter, spacing and soil resistivity.
R_single = (ρ / 2πL) × ln(4L/d)
R_total = R_single / (N × η)
First compute single rod resistance using R = (ρ / 2πL) × ln(4L/d), where ρ is soil resistivity, L is rod length and d is rod diameter. Then for N rods in parallel, apply R_total = R_single / (N × η), where η is the utilization factor (typically 0.6–0.9) that accounts for mutual interference depending on rod spacing.
The ideal spacing between earthing rods is at least equal to the rod length (S ≥ L). This minimizes mutual coupling and maximizes the utilization factor. Greater spacing improves parallel efficiency but requires more land area.
Soil resistivity (ρ) is directly proportional to ground resistance. Higher resistivity soils such as dry sand or rock increase resistance, while moist clay and loam lower it. Measured ρ values typically range from 10 Ω·m for wet clay to over 10,000 Ω·m for dry rock.